REV-8D-330
This premium performance 12V dry series battery is equipped with an AP & 3/8” Stud terminal type and has more capacity than traditional lead-acid batteries, even in extreme conditions. All RELiON R4000 batteries have installation flexibility. These non-hazardous, clean batteries emit no gasses during normal operation. They can be used safely near sensitive equipment or people.
PRODUCT SPECIFICATIONS
- Voltage: 12.0V
- Amp Hours: 330Ah
DIMENSIONS & WEIGHT
- Length: 20.8 in (528 mm)
- Width: 11.1 in (282 mm)
- Height: 9.8 in (250 mm)
- Weight: 182.8 lbs (82.9 kg)
APPLICATIONS
- Backup Power
- Marine
- Recreational Vehicles
- Solar
DATA SHEET
|
Electrical Specifications |
|
|---|---|
| Nominal Voltage | 12 V |
| Capacity @ C100 | 350 Ah |
| Capacity @ C20 | 330 Ah |
| Capacity @ C10 | 300 Ah |
| Capacity @ C5 | 260 Ah |
| Capacity @ 75A | 210 min |
| Capacity @ 25A | 740 min |
| Energy @ C100 | 4200 Wh |
| CA 32 ºF (0 ºC) | 2030 A |
| CCA 0 ºF (-18 ºC) | 1600 A |
| Internal Resistance | 2.5 mΩ |
| Short Circuit Current | 9900 A |
| Self Discharge | <3% per Month |
|
Mechanical & Physical Specifications |
|
|---|---|
| Dimensions (L x W x H) | 20.8 x 11.1 x 9.8” 528 x 282 x 250 mm |
| Weight | 182.8 lbs (82.9 kg) |
| Terminal Type | AP & 3/8” Stud |
| Terminal Torque AP | 44 – 62 in-lbs (5 – 7 N-m) |
| Terminal Torque STUD | 120 – 180 in-lbs (14 – 20 N-m) |
| Battery Type | VRLA |
| Case Material | Polypropolyene |
| Handle | Rope with plastic grip |
|
Temperature Specifications |
|
|---|---|
| Operation/Storage Temperature Range | -4 – 122 ºF (-20 – 50 ºC) |
|
Charge Specifications |
|
|---|---|
| Recommended Charge Current | 33 – 66 A |
| Maximum Charge Current | 83 A |
|
Compliance Specifications |
|
|---|---|
| Certifications | UL1989 |
| Shipping Classification | UN 2800, CLASS 8 |
|
Charge Voltages (12 V System) |
|
|---|---|
| Bulk/Absorption | 14.4 V – 14.7 V |
| Float | 13.6 – 13.8 V |
|
Charge Voltages (24 V System) |
|
|---|---|
| Bulk/Absorption | 28.8 V – 29.4 V |
| Float | 27.2 – 27.6 V |
|
Charge Voltages (36 V System) |
|
|---|---|
| Bulk/Absorption | 43.2 V – 44.1 V |
| Float | 40.8 – 41.4 V |
|
Charge Voltages (48 V System) |
|
|---|---|
| Bulk/Absorption | 57.6 V – 58.8 V |
| Float | 54.4 – 55.2 V |
|
Charge Temperature Compensation |
|
|---|---|
| Cold Temperature Charging | +2.8 mV/cell/ºF +5 mV/cell/ºC |
| Hot Temperature Charging | -2.8 mV/cell/ºF -5 mV/cell/ºC |